| Products |
Wires and Cables |
| Farcom Single Core Flame Retardant Low Smoke (FRLS) PVC Insulated Electrical Wires conforming to IS : 694 Voltage Grade upto 1100 Volts |
| Nominal Cross Sectional Area of Conductor Sq. mm |
Nominal No./Dia of Wires No./mm |
Maximum overall Diameter mm |
Current carrying capacity # 2 Cables, Single Phase |
| In Conduit / Trunking mm |
Clipped direct to surface or on cable tray bunched & unenclosed Amps |
| 1.00 |
14/0.30 * |
2.8 |
11 |
12 |
| 1.50 |
22/0.30 * |
3.2 |
13 |
16 |
| 2.50 |
36/0.30* |
3.8 |
18 |
22 |
| 4.00 |
56/0.30 * * |
4.4 |
24 |
29 |
| 6.00 |
85/0.30 * * |
5.2 |
31 |
37 |
|
Standard Colours : Red, Yellow, Blue, Black, Green, Grey, White. Provided with Orange tracer.
Standard length : 90 meter and 300 meter coils.
* As per conductor class 2 of IS : 8130/1984.
* * As per conductor class 5 of IS : 8130/1984.
Critical Oxygen Index : ≥ 29 %, Temperature Index : ≥ 250°C,
Smoke Density (Light Transmission) ≥ 40%, Acid Gas Generation < 20%. |
| Farcom Single Core Flame Retardant Low Smoke (FRLS) PVC Insulated Heavy Duty Copper Flexibles conforming to IS : 694 Voltage Grade upto 1100 Volts |
| Nominal Cross Sectional Area of Conductor Sq. mm |
Nominal No./Dia of Wires No./mm |
Nominal Thickness of Insulation mm |
Maximum overall Diameter mm |
Current carrying Capacity @ 40°C Ambient Amps |
| 10.00 |
140/0.30 |
1.0 |
6.8 |
51 |
| 16.00 |
126/0.40 |
1.0 |
8.2 |
68 |
| 25.00 |
196/0.40 |
1.2 |
10.6 |
86 |
| 35.00 |
276/0.40 |
1.2 |
11.5 |
110 |
| 50.00 |
396/0.40 |
1.4 |
14.0 |
145 |
| 70.00 |
360/0.50 |
1.8 |
16.2 |
214 |
|
Critical Oxygen Index : ≥ 29%, Temperature Index : ≥ 250°C,
Smoke Density (Light Transmission) ≥ 40%, Acid Gas Generation < 20% |
|